Compact Fluorescent Program Start Series Lamp Operation

Lamp Type No. Of Lamps Lamp Watts Line Voltage Ballast Factor Input Watts Input Current (amps) Power Factor
THD Ballast Efficacy Factor

CF13DE* 2 13 120 1.00 29 0.25 0.99 <10% 3.45
2 13 277 1.00 29 0.11 0.99 <10% 3.45
1 13 120 1.00 16 0.16 0.96 <10% 6.25
1 13 277 1.00 16 0.06 0.96 <10% 6.25

CF13TE 2 13 120 1.00 29 0.25 0.99 <10% 3.45
2 13 277 1.00 29 0.11 0.99 <10% 3.45
1 13 120 1.00 16 0.16 0.96 <10% 6.25
1 13 277 1.00 16 0.06 0.96 <10% 6.25
CF18DE 1 18 120 1.00 20 0.17 0.99 <12% 5.00
1 18 277 1.00 20 0.07 0.97 <12% 5.00
CF18TE 1 18 120 1.00 20 0.17 0.99 <12% 5.00
1 18 277 1.00 20 0.07 0.97 <12% 5.00

CFS10W/GR10q 2 10 120 0.95 23 0.19 0.97 <11% 4.13
2 10 277 0.95 23 0.09 0.97 <11% 4.13
1 10 120 1.05 13 0.11 0.96 <14% 8.08
1 10 277 1.05 13 0.05 0.96 <14% 8.08
CF16W/GR10q 1 16 120 1.00 17 0.14 0.96 <12% 5.88
1 16 277 1.00 17 0.06 0.96 <12% 5.88
F14T5 2 14 120 1.00 31 0.26 0.99 <10% 3.22
2 14 277 1.00 31 0.12 0.98 <10% 3.22
F13T5 2 13 120 1.00 30 0.25 0.99 <10% 3.33
2 13 277 1.00 30 0.11 0.98 <10% 3.33

* Primary Lamp Design Ballast Specifications
• Ballast shall have a five-year warranty with maximum case temperature of
70ºC or three-year warranty with maximum case temperature of 90ºC.
• Ballast shall be UL certified.
• Ballast shall be sound rated Class A.
• Ballast shall be Class P Type 1 Outdoor.
• Ballast shall have a Lamp Current Crest Factor of <1.7.
• Ballast shall withstand line transients as specified in ANSI C62.41.
• Ballast shall comply with the limits of FCC Part 18 Class B (Consumer).
• Ballast shall have a lamp operating frequency greater than 40KHz.
• Ballast shall have color-coded, dual entry poke-in connectors.
• Ballast shall ignite lamps within 900ms.
• Ballast shall have a 0ºF minimum lamp starting temperature for primary lamp(s).
• Ballast shall be Program Start.
• Ballast shall be Series Lamp Operation.
• Ballast shall have a minimum Power Factor of 97% for primary lamp operation.
• Ballast shall operate within a +/- 10% of the ballast specified line voltage at an

This ballast will operation the following lamps:

input frequency of 50Hz or 60Hz.
• Ballast shall have a maximum case hot spot temperature of 90ºC.
• Ballast shall have end of lamp life protection.

DOUBLE (CFDE),
4 PIN 13W

TRIPLE (CFTE),
4 PIN 13W

2D10/16W

• Ballast shall have auto restart.

Wiring Diagram

TOP VIEW
4.63

2.40

SIDE VIEW

BLACK

WHITE

GROUND

BALLAST

BLUE BLUE

YELLOW YELLOW

RED RED

BLUE BLUE

***Cap or remove unused Yellow Leads

HOTSPOT

2.5

• Specifications are subject to change without notice.

Howard Lighting Products | 580 Eastview Drive | Laurel, MS 39443 (toll free) 800.956.3456 | (direct) 601.422.0033 | (fax) 601.422.1652 www.HowardLightingProducts.com

Reviews

There are no reviews yet.

Be the first to review “EP2/13CF/MV/K2- 2 LAMP 13W COMPACT FLUORESCENT”

Top