ep2-ballast howard lighting

EP2/54HO/PRS/MV/W/MC

Availability: In stock

Sku: EP2/54HO/PRS/MV/W/MC

Be the first to review this product

Quick Overview

2 Lamp
Standard Ballast Factor Multi-volt

Quantity

$26.17

EP2-54HO-PRS-MV-W-MC

EP2/54HO/PRS/MV/W/MC

EP2-54HO-PRS-MV-W-MC SPEC SHEET
T5 Programmed Rapid Start Series Lamp Operation

Lamp Type No. Of Lamps Lamp Watts Line Voltage Ballast Factor Input Watts Input Current (amps) Power Factor
THD Ballast Efficacy Factor

F54T5/HO* 2 54 120 1.00 120 1.00 0.98 <10% 0.80
2 54 277 1.00 117 0.43 0.97 <10% 0.80
1 54 120 1.03 62 0.52 0.98 <10% 1.60
1 54 277 1.03 62 0.23 0.90 <20% 1.60

FC12T5/HO 55W 2 55 120 0.86 106 0.87 0.98 <10% 0.80
2 55 277 0.86 103 0.37 0.97 <10% 0.80
1 55 120 0.88 55 0.45 0.98 <10% 1.60
1 55 277 0.88 55 0.20 0.90 <20% 1.60

FT55W/2G11 2 55 120 0.91 112 0.94 0.98 <10% 0.80
2 55 277 0.91 109 0.40 0.97 <10% 0.80
1 55 120 0.93 58 0.51 0.98 <10% 1.60
1 55 277 0.93 58 0.22 0.90 <20% 1.60

FT50W/2G11 2 50 120 1.12 118 1.01 0.98 <10% 0.90
2 50 277 1.12 115 0.43 0.97 <10% 0.90
1 50 120 1.15 61 0.52 0.98 <10% 1.80
1 50 277 0.90 61 0.23 0.90 <20% 1.80

F54T5/HO/ES 2 49 120 0.99 106 0.88 0.98 <10% 0.90
2 49 277 0.98 105 0.38 0.97 <10% 0.90
1 49 120 0.90 53 0.44 0.99 <10% 1.60
1 49 277 1.04 58 0.21 0.90 <10% 1.70

* Primary Lamp Design
Ballast Specifications
• Ballast shall have a five-year warranty
• Ballast shall be UL & cUL 935 Listed, & UL “HL” rated for hazardous locations
• Ballast shall meet RoHS compliance
• Ballast shall be sound rated Class A
• Ballast shall have a Lamp Current Crest Factor of <1.7
• Ballast shall meet ANSI Standards C62.41-2002 & C82.11-2005
• Ballast shall comply with the limits of FCC Part 18 Class A (Non-consumer)

Wiring Diagram

2 Lamp Operation
BLACK

WHITE BALLAST

GROUND

RED RED BLUE BLUE YELLOW YELLOW

• Ballast shall have a lamp operating frequency greater than 42kHz
• Ballast shall have a -18oC minimum lamp starting temperature for primary lamp
• Ballast shall be Program Rapid Start Series Lamp Operation
• Ballast shall have minimum Power Factor of 98% for primary Lamp operation
• Ballast shall operate within +/- 10% of the ballast specified line voltage at 60 Hz
• Ballast shall have a maximum case hot spot temperature of 90 Celsius
• Ballast shall have Lamp End-Of-Life Protection

LINE

LAMP LAMP
1 Lamp Operation
Cap yellow leads
BLACK

WHITE BALLAST

RED RED BLUE BLUE YELLOW YELLOW

Side Ballast View

Bottom Ballast View

Dimensions

L: 9.5”

LINE

GROUND

LAMP

H 0.31 W

M
W L

W: 1.3”
H: 1.0”
M: 9.0”

• Specifications are subject to change without notice.

Howard Lighting Products | 580 Eastview Drive | Laurel, MS 39443 (toll free) 800.956.3456 | (direct) 601.422.0033 | (fax) 601.422.1652 www.HowardLightingProducts.com